Franklin Fueling Systems Colibri CL6 Setup and Operators Guide User Manual
Page 12

12
[Setup] / Fuel Management System / Static Tank Testing
Parameter Name
Parameter Value
Description
Value
Region
United States
Choose United States, Spain or Other (regulatory)
abc#
Monthly Leak Test
Threshold
(0.21)
Set static leak tolerance for monthly testing tanks.
# cc/sec
Yearly Leak Test
Threshold
(0.11)
Set static leak tolerance for yearly testing tanks.
# cc/sec
Sentinel Mode
Threshold
(3.15)
Set static leak tolerance for Sentinel Mode.
# cc/sec
Confidence
(99%)
Leak testing confidence.
90, 95, 97.5,
99 %
Minimum Leak Test
Time
(2 hr)
Minimum amount of time used to test.
0-8
Maximum Leak Test
Time
(8 hr)
Maximum amount of time used to test.
1-8
Alarm On Precision
Leak Test Failure
(No)
Yes will produce an alarm upon leak test failure.
Yes/No
[Setup] / Fuel Management System / Tanks
Parameter Name
Parameter Value Description
Value
Name
(Tank 1)
Given name of tank.
abc#
Type
(Special 1)
Type of tank.
Std./Spcl.
Manifolded
(No)
Part of a tank Manifold?
Yes / No
Product #
(1)
Product # In tank
1-48
Delivery Threshold
(757.1 liter)
Level increase needed to signal delivery
>0.3
Theft Threshold
(18.9 liter)
Level decrease needed to signal theft. Note: console
must be in Sentinel Mode
>0.3
Monthly Compliance
Yes
Track this tank under monthly section of compliance
page.
Yes / No
Annual Compliance
Yes
Track this tank under annual section of compliance
page.
Yes / No
Probe
(See below)
Limits
(See below)
[Setup] / Fuel Management System / Tanks /
Tank 1 / Probe
Parameter
Name
Parameter Value Description
Value
Channel
(Probe 1)
Channel used for the probe in tank.
Probe
Type
(Standard 29)
Type of probe used in this tank.
Std./Spcl.
Ratio
(1 to 1 tip to head) Ratio of product level movement in proportion to
the float
1:1; 7:1; 9:1
Float Type
(4 in gas)
Type of float(s) used on probe.
4, 3, or 2 in.
Gas/Diesel,
Stainless,
LPG, Density
Water Float
Yes
Indicates if water float is on probe.
Yes / No
Gradient
(8.99046 µs/mm) Speed of probe wire.
# µs/mm
Product Offset
(0.00 mm)
Used for compensation of tank tilt.
# mm
Water Offset
(0.00 mm)
Used to compensate for debris on tank bottom.
# mm