24

FMS

Special Product Alarms

Displayed Alarm

Description

Recommended Actions

Alpha Volume

Correction Error

These Alarms refer to temperature correction

coefficients used by the console to calculate

Net Volume. When these values are entered

too high or too low, an alarm condition will

occur.

Verify that the Volume in the Correction Type matches the

specifications of the product used in ‘Special Products’

Programming. These values should be listed in the product

manufacturer’s Spec Sheets.

API Volume

Correction Error

These Alarms refer to temperature correction

coefficients used by the console to calculate

Net Volume. When these values are entered

too high or too low, an alarm condition will

occur.

Verify that the Volume in the Correction Type matches the

specifications of the product used in ‘Special Products’

Programming. These values should be listed in the product

manufacturer’s Spec Sheets.

Level Error

The level of the product float on the probe

listed with the alarm has exceeded a possible

level according to the programming.

Verify that the following parameters are programmed correctly

according to site specifications: Correction Table, Gradient, Probe

Type, and Product Offset.

Net Error

The net volume of the product float on the

probe listed with the alarm has exceeded

a possible volume according to the

programming; related to Volume Correction.

Verify that the following parameters are programmed correctly

according to site specifications: Correction Table, Gradient, Probe

Type, and Product Offset.

Product Volume

Error

The volume of the product float on the probe

listed with the alarm has exceeded a possible

volume according to the programming.

Verify that the following parameters are programmed correctly

according to site specifications: Correction Table, Gradient, Probe

Type, and Product Offset.

Ullage Error

The Ullage level on the tank/manifold listed

with the alarm has exceeded a possible level

according to the programming.

Verify that the following parameters are programmed correctly

according to site specifications: Correction Table, Gradient, Probe

Type, and Product Offset.

Water Volume

Error

The Water Volume on the tank/manifold listed

with the alarm has exceeded a possible level

according to the programming.

Verify that the following parameters are programmed correctly

according to site specifications: Correction Table, Gradient, Probe

Type, and Product Offset.

If the tank is not listed as a standard tank in Appendix B: Standard Tanks Table, use the tank chart from the manufacturer to create a

custom correction table.