Franklin Fueling Systems Colibri CL6 Setup and Operators Guide User Manual
Page 24

24
FMS
Special Product Alarms
Displayed Alarm
Description
Recommended Actions
Alpha Volume
Correction Error
These Alarms refer to temperature correction
coefficients used by the console to calculate
Net Volume. When these values are entered
too high or too low, an alarm condition will
occur.
Verify that the Volume in the Correction Type matches the
specifications of the product used in ‘Special Products’
Programming. These values should be listed in the product
manufacturer’s Spec Sheets.
API Volume
Correction Error
These Alarms refer to temperature correction
coefficients used by the console to calculate
Net Volume. When these values are entered
too high or too low, an alarm condition will
occur.
Verify that the Volume in the Correction Type matches the
specifications of the product used in ‘Special Products’
Programming. These values should be listed in the product
manufacturer’s Spec Sheets.
Level Error
The level of the product float on the probe
listed with the alarm has exceeded a possible
level according to the programming.
Verify that the following parameters are programmed correctly
according to site specifications: Correction Table, Gradient, Probe
Type, and Product Offset.
Net Error
The net volume of the product float on the
probe listed with the alarm has exceeded
a possible volume according to the
programming; related to Volume Correction.
Verify that the following parameters are programmed correctly
according to site specifications: Correction Table, Gradient, Probe
Type, and Product Offset.
Product Volume
Error
The volume of the product float on the probe
listed with the alarm has exceeded a possible
volume according to the programming.
Verify that the following parameters are programmed correctly
according to site specifications: Correction Table, Gradient, Probe
Type, and Product Offset.
Ullage Error
The Ullage level on the tank/manifold listed
with the alarm has exceeded a possible level
according to the programming.
Verify that the following parameters are programmed correctly
according to site specifications: Correction Table, Gradient, Probe
Type, and Product Offset.
Water Volume
Error
The Water Volume on the tank/manifold listed
with the alarm has exceeded a possible level
according to the programming.
Verify that the following parameters are programmed correctly
according to site specifications: Correction Table, Gradient, Probe
Type, and Product Offset.
If the tank is not listed as a standard tank in Appendix B: Standard Tanks Table, use the tank chart from the manufacturer to create a
custom correction table.