Appendix F - Using the Console’s Autocalibration Feature

Using the Autocalibration Feature on an FFS

Tank Gauge

Introduction

Autocal is a feature of the Colibri Tank Monitoring Systems

which generates a tank strapping chart in order to

accurately calibrate and reconcile your fuel management

system automatically. Autocal compares sale of product

from dispensers with changes in tank volume.
Autocal corrects discrepancies in delivery reporting and

daily reconciliations that are caused by inaccurate tank

information programmed into the ATG. Incorrect tank

information can come from:
• Lack of a tank chart
• Wrong tank chart
• Tank that deforms over time and no longer represents

its tank chart

Autocal Requirements

A high variance on a tank’s Daily Reconciliation Reports,

means that the amount of product flowing through the

dispensers appears to be different from the amount leaving

the tank. This could mean that the manufacturer’s tank

chart programmed into the ATG is not accurate, but it can

also be caused by several other things. The following

items should always be checked by a certified service

professional before starting Autocal:
• Autocal

cannot be performed on manifolded tanks

• Probes must be properly installed
• Tank tilt calculations must be correct (or 0 if the probe is

at tank center)

• The tank charts provided must be correct
• The tank must be programmed correctly (length,

diameter, correction points)

• Make sure that probe alarms or TS-DIM (Dispenser

Interface Module) problems are not the reason for the

Over / Short status

• Recently passed tank tests and line tests are on file
• The dispenser meters are calibrated
• Your FFS ATG has the Reconciliation option and is

interfaced with a POS / dispenser

• Your FFS ATG has the correct Reconciliation

programming

Note: Calibrating a tank with Autocal that does not meet

the above criteria could potentially cover up a

problem or leak.

Hardware and Software Requirements

An Colibri gauge must have the TS-TRAC internal

software option to perform the Autocal feature. The Colibri

Tank Monitoring System must be doing accurate dispenser

reconciliation.
Autocal Preparation

Determining Sites That May Require Autocal. The following

steps will help determine if an Autocalibration may be

necessary

1. Generate a DIM Reconciliation Report for the last

30 days. Look for tanks that have Over or Short

status on the report.

2. Take note if any days show missing sales or sales

numbers that are unrealistic. These days may

be the reason that the status may show OVER

or SHORT, but they are not reasons for using

Autocal. It is possible that the tank still needs to

be calibrated even if it has some missing days

or data. The “good” days need to be examined

to see if the Daily Variance is usually high. If the

Daily Variance is greater than 10% of the sales

on “good” days, then there is another problem in

the system that needs to be fixed prior to starting

Autocal.