Appendix A: List of Alarms
FMS
Tank/Manifold Alarms
Displayed Alarm
Description
Recommended Actions
Correction Table
Error
Correction points for the special tank
listed with the alarm were not entered
or were entered incorrectly.
Verify that the correction table points for the tank listed with the
alarm are entered sequentially in ‘Special Tanks’ Programming.
Manifold Gross Leak
Detected
The manifold listed with the alarm has
failed a Gross Leak Test.
Review manifold leak test history and programming. It may be
necessary to manually start a Gross Leak Test to keep the manifold
in compliance.
Manifold Leak
Detected
The manifold listed with the alarm has
failed a Monthly Leak Test.
Review manifold leak test history and programming. It may be
necessary to manually start a Monthly Leak Test to keep the
manifold in compliance.
Manifold SCALD Leak
Detected
The manifold listed with the alarm has
failed a SCALD Leak Test.
Review manifold leak test history diagnostic web page and
programming.
Manifold Theft
Detected
Product level in the manifold listed
with the alarm has dropped below the
programmed Theft Limit.
Verify that the programmed Theft limit is correct. Verify that the
values of product loss on the console correspond with actual
product loss in the tank.
Tank Gross Leak
Detected
The manifold listed with the alarm has
failed a Gross Leak Test.
Review manifold leak test history and programming. It may be
necessary to manually start a Gross Leak Test to keep the tank in
compliance.
Tank Leak Detected
The tank listed with the alarm has
failed a Monthly Leak Test.
Review tank leak test history and programming. It may be
necessary to manually start a Monthly Leak Test to keep the tank in
compliance.
Tank SCALD Leak
Detected
The tank listed with the alarm has
failed a SCALD Leak Test.
Review tank leak test history and programming. Test to keep the
tank in compliance.
Tank Theft Detected
Product level in the tank listed with
the alarm has dropped below the
programmed Theft Limit.
Verify that the programmed Theft Limit is correct. Verify that the
values of product loss on the console correspond with actual
product loss in the tank.