beautypg.com

Franklin Fueling Systems Colibri CL6 Setup and Operators Guide User Manual

Page 14

background image

14

[Setup] / Fuel Management System / Products

Product #
Name

(Product 1)

Enter Product name

abc#

Type

(Unleaded

Regular)

Select type of fuel

Unleaded Regular, Plus,

Extra, Super, Diesel,

Kerosene, #2 Fuel Oil,

Ethanol, Special #
(20 Characters maximum)

[Setup] / Fuel Management System / Grades

Grade #
First Tank

(Tank 1)

Select tank number for first tank

Tank 1-6

Second tank

(none)

Select tank number for second tank

None, Tank 1-6

[Setup] / Fuel Management System / Reconciliation

Parameter

Parameter Value

Description

Value

Over Short Limit

Percent

(1.00)

Enter short limit percent

0-100

Over Short Limit

Volume

(130)

Enter short limit volume

#

Sales

yes

Include Sales

Yes / No

Deliveries

Yes

Include Deliveries

Yes / No

Tank Volume

Yes

Include tank volume

Yes / No

[Setup] / Fuel Management System / Autocalibration

Note: Must have Dispenser Interface connected for Autocalibration to work

Parameter

Parameter Value

Description

Value

Autostop Volume

Coverage

(100)

Enter volume percent at which the Autocalibration

will automatically stop.

0-100

Autostop Level

Coverage

(80)

Enter level percent at which the Autocalibration

will automatically stop.

0-100

Autostop Number of

Points Coverage

(100)

Enter number of points required at which the

Autocalibration will automatically stop.

0-100

Any of these parameters values can be set separately. If any of the values are met the autocalibration will stop.
• If you want a certain volume coverage, set volume to desired percentage and level and number of points to 100.
• If you want a certain level coverage, set level to desired percentage and set volume and number of points to 100.
• If you want so many points in the table, set number of points to desired number and set volume and level coverage to 100.
If you have accurate tank dimensions entered, you may not need Autocalibration. Refer to Appendix F for detailed

information on setting up and running Autocalibration.