5 - 6
Tank Sentinel Operator’s Guide
TABLE 5 - 1 (C
ONTINUED
... )
ALARMS & ERROR MESSAGES
NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
55
RTC FAILURE
SYSTEM
Real Time Clock has failed. Clock and Calendar
settings are affected. Verify date and time are
correct (use CHECK key). Change settings as
needed. Cycle power. Verify settings (use CHECK
key).
56
RTD TABLE ERROR / RTD
TBL ER / RTD TBL
SYSTEM
WARNING - Number of RTDs Error does not
match actual / setup - programmed value
(call
service provider to correct this problem)
57
SCALD TEST FAILED /
SCALD DETECTED LEAK
SYSTEM
WARNING - SCALD Leak Test Failed alarm report
for Tank N
(run a Standard leak test for that
tank... See LEAK)
58
SEN DAT / SENS DATA /
SENSOR DATA ERROR
SYSTEM
WARNING - a BriteSensor @ Channel #N is
sending data errors
(call service provider ASAP)
59
SENS LOSS OF SIGNAL /
SIG LOST / SEN SIG
SYSTEM
WARNING - no data sent / signal lost from
BriteSensor @ Channel #N
(call service provider
ASAP to correct this)
60
SENSOR ID ERROR /
SENSOR ID / SENS ID
SYSTEM
WARNING - a Standard sensor or BriteSensor
was incorrectly typed / identified
(call your service
provider to correct this)
61
SENSOR SYNC ERROR /
SENSOR SYNC / SEN SYN
SYSTEM
WARNING - data signals not synchronous from
BriteSensor @ Channel #N
(call service provider
ASAP to correct this)
62
CORRECTION (STRAPPING)
TABLE ERROR / TABLE ERR
/ TBL ERR
SYSTEM
WARNING - Tank Strapping Chart or Table...
setup Error (call service provider to correct)
63
TEMPERATURE ERROR /
TEMP ERROR / TMP ERR
SYSTEM
WARNING - probe/product Temperature -
calculation Error (TMP ERR
call service provider
to correct this problem)
64
THEFT DETECTED / THEFT
LIMIT
SYSTEM
WARNING - Sentinel Mode: Theft Detected (the
amount of product missing reached the Theft Limit)
alarm report for Tank N
65
TS-SEM FUSE OPEN / SEM
FUS / SEM FUSE
SYSTEM
WARNING - TS-SEM FUSE OPEN @ BriteBox #1
or #2... [#1 is closest to the console] there is no 5
VDC …Leak Detection Sensors wired to the
BriteBox won't function !
(call service provider to
troubleshoot/replace TS-SEM FUSE F1)
66
UNSTABLE PROBE / UNST
PROBE / UNST PB / UNST
PB
SYSTEM
WARNING - the signal from Probe N has become
Unstable
(call service provider to correct)
67
VOLUME ERROR / VOLUME
ERR / VOL ERR (also see
level, net, ullage, water error)
SYSTEM
WARNING - product - Volume calculation error
(Error in programming: tank shape / probe type /
special probe - OR - no level signal from probe.
Call service provider to correct this.)