Tank Sentinel Operator’s Guide

TABLE 5 - 1 (C

ONTINUED

... )

ALARMS & ERROR MESSAGES

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

55

RTC FAILURE

SYSTEM

Real Time Clock has failed. Clock and Calendar
settings are affected. Verify date and time are
correct (use CHECK key). Change settings as
needed. Cycle power. Verify settings (use CHECK
key).

56

RTD TABLE ERROR / RTD
TBL ER / RTD TBL

SYSTEM

WARNING - Number of RTDs Error does not
match actual / setup - programmed value

(call

service provider to correct this problem)

57

SCALD TEST FAILED /
SCALD DETECTED LEAK

SYSTEM

WARNING - SCALD Leak Test Failed alarm report
for Tank N

(run a Standard leak test for that

tank... See LEAK)

58

SEN DAT / SENS DATA /
SENSOR DATA ERROR

SYSTEM

WARNING - a BriteSensor @ Channel #N is
sending data errors

(call service provider ASAP)

59

SENS LOSS OF SIGNAL /
SIG LOST / SEN SIG

SYSTEM

WARNING - no data sent / signal lost from
BriteSensor @ Channel #N

(call service provider

ASAP to correct this)

60

SENSOR ID ERROR /
SENSOR ID / SENS ID

SYSTEM

WARNING - a Standard sensor or BriteSensor
was incorrectly typed / identified

(call your service

provider to correct this)

61

SENSOR SYNC ERROR /
SENSOR SYNC / SEN SYN

SYSTEM

WARNING - data signals not synchronous from
BriteSensor @ Channel #N

(call service provider

ASAP to correct this)

62

CORRECTION (STRAPPING)
TABLE ERROR / TABLE ERR
/ TBL ERR

SYSTEM

WARNING - Tank Strapping Chart or Table...
setup Error (call service provider to correct)

63

TEMPERATURE ERROR /
TEMP ERROR / TMP ERR

SYSTEM

WARNING - probe/product Temperature -
calculation Error (TMP ERR

call service provider

to correct this problem)

64

THEFT DETECTED / THEFT
LIMIT

SYSTEM

WARNING - Sentinel Mode: Theft Detected (the
amount of product missing reached the Theft Limit)
alarm report for Tank N

65

TS-SEM FUSE OPEN / SEM
FUS / SEM FUSE

SYSTEM

WARNING - TS-SEM FUSE OPEN @ BriteBox #1
or #2... [#1 is closest to the console] there is no 5
VDC …Leak Detection Sensors wired to the
BriteBox won't function !

(call service provider to

troubleshoot/replace TS-SEM FUSE F1)

66

UNSTABLE PROBE / UNST
PROBE / UNST PB / UNST
PB

SYSTEM

WARNING - the signal from Probe N has become
Unstable

(call service provider to correct)

67

VOLUME ERROR / VOLUME
ERR / VOL ERR (also see
level, net, ullage, water error)

SYSTEM

WARNING - product - Volume calculation error
(Error in programming: tank shape / probe type /
special probe - OR - no level signal from probe.
Call service provider to correct this.)