Tank Sentinel Operator’s Guide
Visual Alarm
Indications
The console has 4 visual output devices:
1) Light green, 80 character display
2) Yellow warning light (Status Row)
3) Red alarm light (Status Row)
4) Printer reports – printout if enabled / programmed
and if the printer has paper
The console display will show a
WARNING
message under the word SYSTEM when a
system fault occurs. An
ALARM
message will appear under one of the TANK or SENSOR
or LINE columns when one of those alarms happen.
The status row will indicate System faults by causing the yellow
WARNING
light to flash
/ turn-on. In addition, the
ALARM
light will flash when an alarm is detected. (See Status
Row indicators below.)
Visual warnings and alarms act independently from the custom-programmed audio or
printed alarms. The Status Row Indicator lights have 3 different states, they are:
1.)
>
Flashing
<
until active, cleared, or transient faults are acknowledged, then
2.)
On-steady
(solid) once active warnings or alarms are acknowledged, then
3.)Off
after all active faults have cleared and have been acknowledged
Depending on how the system was programmed, alarms may, or may not activate the audio
alarm horn when a warning or alarm occurs. Flashing Warning or Alarm lights indicate
that at least one or more new alarms exist since the last time that alarms were
acknowledged. Routinely check the Status Row indicators and printed reports for new
alarms.
POWER
ALARM
TEST
WARNING
ALARM
NOTE
☞
NOTE: TANK AND
LINE STATUS COLUMNS
APPEAR ONLY IF THE
NUMBER OF TANKS OR
LINES ARE
PROGRAMMED TO A
VALUE OTHER THAN
ZERO.
➂
Status Row
indicators
SYSTEM
TANK
SENSOR
LINE
WARNING
TESTING
ALARM
OKAY
M1
M2
M3
M4
LEFT
RIGHT