2 connectors for external wiring, Fig. 15 standard connections for external wiring – GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual
Page 14

4.2 Connectors for external wiring.
Closing drive supply (~,+) (S3)
Closing drive supply (N,-)
PE
(+) (-)
1
2
3
4
5
6
7
8
9 10 11 12
X2
-S3 ed imoulse coil firing signal 6…24
-S1 ( signal for CLOSE)
-S2 ( signal for OPEN by 1st shunt trip)
-S2 ( signal for OPEN by 2nd shunt trip)
Wiring to -X2 connector if shunt trip installed.
Closing drive supply (~,+) (S3)
Closing drive supply (N,-)
PE
(+) (-)
1
2
3
4
5
6
7
8
9 10 11 12
X2
-S3 ed imoulse coil firing signal 6…24
-S1 ( signal for CLOSE)
-S2 ( signal for OPEN by 1st UVR)
-S2 ( signal for OPEN by 2nd UVR)
Wiring to -X2 connector if zero release installed.
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
X3
E
x
ternal
Control
V
o
ltage S
uppl
y (+
)
E
x
ternal
Control
V
o
ltage S
uppl
y (-)
1st NE
K
O
chargi
ng i
ndi
cator
(i
ndi
cates C-bank chargi
ng)
2nd NE
K
O
chargi
ng i
ndi
cator
(i
ndi
cates C-bank chargi
ng)
P
O
CT tri
p
si
gnal
A
rc chute presence i
ndi
cator
Wiring to –X3 connector.
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
X4
HS 1
HS 2
HS 3
HS 4
HS 5
Wiring to –X4 connector.
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
X5
HS 6
HS 7
HS 8
HS 9
Wiring to –X5 connector .
Fig. 15 Standard connections for external wiring.
14
Design and specifications are subject to change without notice
DTR01807 rev.02 2010-02-16