3 technical data tables – GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual
Page 11

3.3 Technical data tables
Table 1. Technical data, type Gerapid 8007R & Gerapid 10007R
Parameter
Reference
Gerapid 8007 R
Gerapid 10007 R
Arc
chute
type
N/A
1x2 1x3 1x2 1x3
Rated continuous current [A]
ANSI C37.14 p.5.3
6.000
6.000 8.000 8.000
2
hours
current
[A]
N/A
7.200 7.200 9.600 9.600
2 minutes current [A]
N/A
12.000
12.000
16.000
16.000
20 seconds current [A]
N/A
18.000
18.000
24.000
24.000
Rated short-time current (250ms) [kA]
ANSI C37.14 p.5.5
90 (149 peak)
60 (100 peak)
90 (149 peak)
60 (100 peak)
Rated maximum voltage [V]
ANSI C37.14 p.5.2
800
1200
800
1.200
Rated insulation voltage - U
Nm
[V]
EN 50124-1 p.1.3.2.4
2.000 2.000 2.000 2.000
Rated impulse voltage - U
Ni
[kV]
EN 50124-1 p.1.3.2.7
18 [1,2/50 µs]
18 [1,2/50 µs]
18 [1,2/50 µs]
18 [1,2/50 µs]
Power frequency voltage – U
a
[kV]
EN 50124-1 a.B 2.2
10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz]
Mechanical endurance [cycles]
N/A
10.000 10.000 10.000 10.000
Rated short circuit peak / sustained current [kA]
ANSI C37.14 p.5.4
200 / 120
132 / 80
200 / 120
132 / 80
Short-circuit characteristic
Tests a, b, c, d ANSI C37.14 annex A
High-speed High-speed High-speed High-speed
Maximum arc voltage [V]
N/A
2.500
2.500
2.500
2.500
Mass ca.
N/A
220 kG
220 kG
220 kG
220 kG
a)
10.000 cycles without parts replacement. Inspection after 5.000 cycles. Max. 5.000 cycles by means of ED impulse coil or POCT release.
c)
Trip by means of POCT (direct-acting, instantaneous, electromechanical and polarized OC release) or by means of ED impulse coil with no intentional delay.
2010-02-16 DTR01807 rev.02
Design and specifications are subject to change without notice
11