O-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed network. Only the selections valid
for the network installed in slot A will be visible in the keypad
display.
Option:
Function:
[0]
*
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
O-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits
12 – 15 in the status word.
[0]
No function
[1]
*
Profile Default Function corresponds to the profile default
selected in O-10 Control Word Profile.
O-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the network.
[0]
Digit
Input
Activates Coast command via a digital input.
[1]
Bus
Activates Coast command via the serial
communication port or network option module.
[2]
Logic
AND
Activates Coast command via the network/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Coast command via the network/serial
communication port OR via one of the digital
inputs.
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the network.
Option:
Function:
[0]
Digital Input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
O-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the network.
[0]
Digit
Input
ActivatesDC Brake command via a digital input.
[1]
Bus
ActivatesDC Brake command via the serial
communication port or network option module.
[2]
Logic
AND
ActivatesDC Brake command via the network/
serial communication port, AND additionally via
one of the digital inputs.
O-52 DC Brake Select
Option:
Function:
[3]
*
Logic OR
ActivatesDC Brake command via the network/
serial communication port OR via one of the
digital inputs.
O-53 Start Select
Option:
Function:
Select control of the drive start function via the
terminals (digital input) and/or via the network.
[0]
Digit
Input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or network option module.
[2]
Logic
AND
Activates Start command via the network/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the network/serial
communication port OR via one of the digital
inputs.
O-54 Reversing Select
Option:
Function:
[0]
Digital
Input
Select control of the drive reverse function via
the terminals (digital input) and/or via the
network.
[1]
Bus
Activates the Reverse command via the serial
communication port or network option
module.
[2]
Logic AND
Activates the Reverse command via the
network/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the Reverse command via the
network/serial communication port OR via one
of the digital inputs.
O-55 Set-up Select
Option:
Function:
Select control of the drive set-up selection via
the terminals (digital input) and/or via the
network.
[0]
Digit
Input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or network option module.
[2]
Logic
AND
Activates the set-up selection via the network/
serial communication port, AND additionally via
one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the network/
serial communication port OR via one of the
digital inputs.