8 parameters, 1 parameter group o-## communication and option – GE Industrial Solutions AF-650 GP PROFINET User Manual
Page 39

8 Parameters
8.1 Parameter Group O-## Communication and Option
O-01 Control Site
Option:
Function:
The setting in this parameter overrides
the settings in O-50 Coasting Select to
O-56 Preset Reference Select.
[0]
*
Digital and
ctrl.word
Control by using both digital input and
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword only
Control by using control word only.
O-03 Control Word Timeout Time
Range:
Function:
1.0 s
*
[0.1 -
18000.0 s]
Enter the maximum time expected to pass
between the reception of two consecutive
messages. If this time is exceeded, it
indicates that the serial communication has
stopped. The function selected in
O-04 Control Word Timeout Function will
then be carried out. The time-out counter is
triggered by a valid control word.
O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time
period specified in O-03 Control Word Timeout Time.
Option:
Function:
[0]
*
Off
Resumes control via serial bus (network or
standard) using the most recent control
word.
[1]
Freeze output Freezes output frequency until communi-
cation resumes.
[2]
Stop
Stops with auto restart when communi-
cation resumes.
[3]
Jogging
Runs the motor at JOG frequency until
communication resumes.
[4]
Max. speed
Runs the motor at maximum frequency
until communication resumes.
[5]
Stop and trip
Stops the motor, then resets the drive in
order to restart: via the network, via the
reset button on the keypad or via a digital
input.
[7]
Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
time-out. If communication resumes causing
the time-out situation to disappear,
O-05 End-of-Timeout Function defines
whether to resume the set-up used before
O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time
period specified in O-03 Control Word Timeout Time.
Option:
Function:
the time-out or to retain the set-up
endorsed by the time-out function.
[8]
Select setup 2 See [7] Select setup 1
[9]
Select setup 3 See [7] Select setup 1
[10]
Select setup 4 See [7] Select setup 1
[26]
Trip
NOTE
The following configuration is required in order to change
the set-up after a time-out:
Set K-10 Active Set-up to [9] Multi set-up and select the
relevant link in K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid
control word following a time-out. This
parameter is active only when O-04 Control
Word Timeout Function is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in O-04 Control
Word Timeout Function and displays a
warning, until O-06 Reset Control Word
Timeout toggles. Then the drive resumes its
original set-up.
[1]
*
Resume set-
up
Resumes the set-up active prior to the time-
out.
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been
selected in O-05 End-of-Timeout Function.
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in O-04 Control
Word Timeout Function, following a control
word time-out.
[1]
Do reset
Returns the drive to the original set-up
following a control word time-out. The drive
performs the reset and then immediately
reverts to the Do not reset [0] setting
Parameters
PROFINET Operating Instruction
38