6.5 GE Drive Control Profile
6.5.1 Control Word according to Drive
Profile (CTW)
To select GE Drive protocol in the control word,
O-10 Control Word Profile must be set to GE Drive protocol
[0]. The control word is used to send commands from a
master (PLC or PC) to a slave (frequency converter).
Please refer to 9 Application Examples for an example of a
control word message using PPO type 3.
Bit
Bit value = 0
Bit value = 1
00
Reference value
external selection lsb
01
Reference value
external selection msb
02
DC brake
Accel/Decel
03
Coasting
No coasting
04
Quick stop
Accel/Decel
05
Hold output frequency
Use Accel/Decel
06
Accel/Decel stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Accel/Decel 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
selection lsb
14
Parameter set-up
selection msb
15
No function
Reverse
Table 6.9
Explanation of the Control Bits
Bits 00/01 Reference value
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in C-05 Multi-
step Frequency 1 - 8 according to Table 6.10:
NOTE
In O-56 Preset Reference Select a selection is made to define
how Bit 00/01 gates with the corresponding function on
the digital inputs.
Programmed
ref. value
Parameter
Bit 01
Bit 00
1
C-05 Multi-step
Frequency 1 - 8 [0]
0
0
2
C-05 Multi-step
Frequency 1 - 8 [1]
0
1
3
C-05 Multi-step
Frequency 1 - 8 [2]
1
0
4
C-05 Multi-step
Frequency 1 - 8 [3]
1
1
Table 6.10
How to Control the Frequenc...
PROFINET Operating Instruction
29
6