Depending on the setting of F-50 Reference Range the reference and MAV are scaled accordingly:
Illustration 6.2
NOTE
If F-50 Reference Range is set to [0] Min - Max, a negative reference will be handled as 0%.
The actual output of the frequency converter is limited by the speed limit parameters in F-18 Motor Speed Low Limit [RPM]
to F-15 Motor Speed High Limit [Hz].
The final speed limit is set by F-03 Max Output Frequency 1.
The reference and the MAV have the format which appears
from the table
MRV / MAV
Integer in hex
Integer in decimal
100%
4000
16.384
75%
3000
12.288
50%
2000
8.192
25%
1000
4.096
0%
0
0
-25%
F000
-4.096
-50%
E000
-8.192
-75%
D000
-12.288
-100%
C000
-16.384
Table 6.4
NOTE
Negative numbers are formed as two's complement.
NOTE
The data type for MRV and MAV is a N2 16 bit
standardised value, meaning it can express a range from
-200% to +200% (8001 to 7FFF).
H-40 Configuration Mode set to [0] Speed open loop.
F-50 Reference Range set to [0] Min - Max.
F-52 Minimum Reference set to 100 RPM.
F-53 Maximum Reference set to 3000 RPM.
MRV / MAV
Actual Speed
0%
0 hex
100 RPM
25%
1000 hex
825 RPM
50%
2000 hex
1550 RPM
75%
3000 hex
2275 RPM
100%
4000 hex
3000 RPM
Table 6.5
6.2.4 Process Control Operation
In process control operation H-40 Configuration Mode is set
to [3] Process.
The reference range in F-50 Reference Range is alway [0]
Min - Max.
- MRV represents the process setpoint.
- MAV expresses the actual process feedback (range +/-
200%).
How to Control the Frequenc...
PROFINET Operating Instruction
24
6