Car2012te series rectifier, Data sheet, Environmental specifications – GE Industrial Solutions CAR2012TE series User Manual
Page 6: Emc compliance

GE
Data Sheet
CAR2012TE series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
February 9, 2014
©2013 General Electric Company. All rights reserved.
Page 6
Environmental Specifications
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
-10
70
°C
Derated above 50C
Storage Temperature
-40
85
°C
Operating Altitude
2250/7382
m/ft
Non-operating Altitude
8200/30k
m / ft
Power Derating with Temperature
2.5
%/°C
50C to 70C
Power Derating with Altitude
2.0
C/301 m
C/1000 ft
Above 2250 m/7382 ft
Acoustic noise
55
45
dbA
Full load
Half load
Over Temperature Protection
125/110
°C
Shutdown / restart
Humidity
Operating
Storage
30
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration
Meet IPC 9592 Class II, Section 5 requirements
EMC Compliance
Parameter
Function
Standard
Level
Criteria
Test
AC input
Conducted
emissions
EN55022, FCC part 15
EN61000-3-2
A*
0.15
–
30MHz
0 – 2 KHz
Radiated
emissions**
EN55022
A*
30 – 10000MHz
AC input
immunity
Voltage dips
EN61000-4-11
A
-30%, 10ms
B
-60%,
100ms
B
-100%,
5sec
Voltage surge
EN61000-4-5
A
4kV, 1.2/50µs, common mode
A
2kV, 1.2/50µs, differential mode
Fast transients
EN61000-4-4
A
5/50ns, 2kV (common mode)
Enclosure
immunity
Conducted RF
fields
EN61000-4-6
A
130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields
EN61000-4-3
A
10V/m, 80-1000MHz, 80% AM
ENV 50140
A
ESD
EN61000-4-2
B
4kV contact, 8kV air
*
Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
**
Radiated emissions compliance is contingent upon the final system configuration.
Criteria Performance
A
No performance degradation
B
Temporary loss of function or degradation not requiring manual intervention
C
Temporary loss of function or degradation that may require manual intervention
D
Loss of function with possible permanent damage