Car2012te series rectifier, Data sheet, Read back descriptions – GE Industrial Solutions CAR2012TE series User Manual
Page 13
![background image](/manuals/295187/13/background.png)
GE
Data Sheet
CAR2012TE series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
February 9, 2014
©2013 General Electric Company. All rights reserved.
Page 13
STATUS_BYTE (0x78) :
Returns one byte of information with a
summary of the most critical device faults.
Bit
Position
Flag
Default
Value
7 Busy 0
6 OFF 0
5 VOUT
Overvoltage 0
4 IOUT
Overcurrent 0
3 VIN
Undervoltage 0
2 Temperature 0
1
CML (Comm. Memory Fault)
0
0
None of the above
0
STATUS_WORD (0x79):
Returns status_byte as the low byte
and the following high_byte.
Bit
Position
Flag
Default
Value
7
VOUT fault or warning
0
6
IOUT fault or warning
0
5 INPUT 0
4 MFR
SPECIFIC 0
3 nPOWER_GOOD 0
2 FANS 0
1 OTHER 0
0 UNKNOWN 0
STATUS_VOUT (0x7A):
Returns one byte of information of
output voltage related faults.
Bit
Position
Flag
Default
Value
7
VOUT OV Fault
0
6 VOUT_OV_WARNING 0
5 VOUT_UV_WARNING 0
4
VOUT UV Fault
0
3 - 0
Not supported
0
STATUS_IOUT (0x7B):
Returns one byte of information of
output current related faults.
Bit
Position
Flag
Default
Value
7
IOUT OC Fault
0
6 Not
supported 0
5
IOUT OC Warning
0
4- 0
Not supported
0
STATUS_INPUT (0x7C):
Returns one byte of information of
input voltage related faults.
Bit
Position
Flag
Default
Value
7 VIN_OV_Fault 0
6 VIN_OV_Warning 0
5 VIN_UV_
Warning 0
4 VIN_UV_Fault 0
3 - 0
Not supported
0
STATUS_TEMPERATURE (0x7D):
Returns one byte of
information of temperature related faults.
Bit
Position
Flag
Default
Value
7 OT
Fault 0
6 OT
Warning 0
5 - 0
Not supported
0
STATUS_CML (0x7E):
Returns one byte of information of
communication related faults.
Bit
Position
Flag
Default
Value
7 Invalid/Unsupported
Command 0
6 Invalid/Unsupported
Data 0
5
Packet Error Check Failed
0
4 - 2
Not supported
0
1
Other Communication Fault
0
0 Not
supported 0
STATUS_FAN_1_2 (0x81) :
Returns one byte of information
with a summary of the most critical device faults.
Bit
Position
Flag
Default
Value
7
Fan 1 Fault
0
6
Fan 2 Fault
0
5 - 4
Not supported
0
3
Fan 1 speed overwritten
0
2
Fan 2 speed overwritten
0
1 - 0
Not supported
0
Read back Descriptions
Single parameter read back:
Functions can be read back one
at a time using the read_word_protocol with PEC. A
command is first sent out notifying the slave what function is
to be read back followed by the data transfer.
Analog data is always transmitted LSB followed by MSB. A NA
following the PEC byte signifies that the transmission is
complete and is being terminated by the ‘host’.
1 8 1
8 1
S Slave
address Wr A Command
Code A
1 8 1
Sr Slave
address Rd A
8
1
8
1 8 1 1
LSB A MSB A
PEC NA P
Read_fan_speed 1 & 2 (0x90, 0x91):
Reading the fan speed is
in Linear Mode returning the RPM value of the fan.