Car2012te series rectifier, Data sheet, Absolute maximum ratings – GE Industrial Solutions CAR2012TE series User Manual
Page 2: Electrical specifications
GE
Data Sheet
CAR2012TE series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
February 9, 2014
©2013 General Electric Company. All rights reserved.
Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure
to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Symbol
Min
Max
Unit
Input Voltage: Continuous
V
IN
0 264
V
AC
Operating Ambient Temperature
T
A
-10 70 °C
Storage Temperature
Tstg
-40
85
°C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
2121
V
DC
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Symbol
Min
Typ
Max
Unit
Operational Range
V
IN
85 115/230 264
V
AC
Frequency Range (ETSI 300-132-1 recommendation)
F
IN
47 50/60 63
Hz
Main Output Turn OFF
V
IN
75 82
V
AC
Main Output Turn ON
80
88
Hysteresis between turn OFF and turn ON
3
5
Maximum Input Current (V
O
= V
O, set
, I
O
=I
O, max
) V
IN
= 100V
AC
I
IN
15.5
12.5
A
AC
V
IN
= 180V
AC
Cold Start Inrush Current (Excluding x-caps, 25C, <10ms,
per ETSI 300-132)
I
IN
40
A
PEAK
Efficiency (T
amb
=25C, V
O
= 12V) V
IN
100% load
50% load
20% load
10% load
115V / 230V
92 / 93.0
93 / 95.0
91 / 94.0
85 / 91.0
%
Power Factor (V
IN
=115/230V
AC
), I
O
= 50% I
O, max
I
O
= I
O, max
PF 0.98
0.99
Holdup time (Vout = 12.0V
DC
, Tamb 25C, I
O
=80% I
O, max
)
V
in
= 230V
AC
V
IN
= 100V
AC
T
12
20
ms
Early warning prior to output falling below regulation
1
(Vout = 12.0V
DC
, Tamb 25C, I
O
=80% I
O, max
)
2
Ride through
T
10
Leakage Current (V
IN
= 250V
AC
, F
IN
= 60Hz)
I
IN
3 mA
RMS
Isolation Input/Output
3000
V
AC
Input/Frame
2121
V
DC
Output/Frame
100
V
DC
12V
dc
MAIN OUTPUT
Parameter
Symbol
Min
Typ
Max
Unit
Output Power 180 – 264 / 90-132 Vac
W
0 -
2000/1300
W
V
AC
≤ 90V
AC
0 - 1200 W
Set point
V
O
11.9 12.00 12.1
V
DC
Overall regulation (load, temperature)
-2
+2
%
1
Measured by the DC_OK signal going LO prior to the output decaying below 10.8Vdc