Car2012te series rectifier, Data sheet, Feature specifications (continued) – GE Industrial Solutions CAR2012TE series User Manual
Page 5: Digital interface specifications

GE
Data Sheet
CAR2012TE series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
February 9, 2014
©2013 General Electric Company. All rights reserved.
Page 5
Feature Specifications (continued)
Parameter
Symbol
Min
Typ
Max
Unit
SMBAlert# (Interrupt)
(must be pulled up externally to Stndby)
Logic High (No Alert - normal)
I
OH
20 µA
V
OH
0.7V
DD
12 V
DC
Logic Low (Alert is set)
I
OL
4 mA
V
OL
0
0.4 V
DC
Output current monitor (Imon)
Resolution
18
mV/A
Measurement range
I
O
0 167
A
DC
Measurement accuracy, load > 25% of FL, V
O
= 12V
DC
-4
+4
%
Analog output range
V
mon
0 3.3
V
DC
Sourced output current
I
O
5 mA
DC
Digital Interface Specifications
Parameter
Conditions
Symbol
Min
Typ
Max
Unit
PMBus Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)
V
IH
0.7V
DD
3.6 V
Input Logic Low Voltage (CLK, DATA)
V
IL
0 0.8 V
Input high sourced current (CLK, DATA)
I
IH
0 10 μA
Output Low sink Voltage (CLK, DATA, SMBALERT#)
I
O
=5mA V
OL
0.4 V
Output Low sink current (CLK, DATA, SMBALERT#)
I
OL
5 mA
Output High open drain leakage current (CLK,DATA,
SMBALERT#)
V
O
=3.6V I
OH
0 10 μA
PMBus Operating frequency range
F
PMB
10 400 kHz
Measurement System Characteristics
Clock stretching
t
STRETCH
25
ms
I
OUT
measurement range
Linear mode
I
RNG
0 167 A
I
OUT
measurement accuracy 25°C
I
ACC
-5 +5 %
V
OUT
measurement range
Linear mode
V
OUT(rng)
0 14 V
V
OUT
measurement accuracy
V
OUT(acc)
-5 +5 %
Temp measurement range
Linear mode
Temp
(rng)
0 125
C
Temp measurement accuracy
3
Temp
(acc)
-5 +5 %
I
IN
measurement range
Linear mode
I
IN(rng)
0 18 A
rms
I
IN
measurement accuracy
I
IN(acc)
-5 +5 %
V
IN
measurement range
Linear mode
V
IN(rng)
0 300 V
rms
V
IN
measurement accuracy
V
IN(acc)
-5 +5 %
P
IN
measurement range
Linear mode
P
N(rng)
0 3000 W
P
IN
measurement accuracy
P
IN(acc)
-5 +5 %
Fan Speed measurement range
Linear mode
0 30k RPM
Fan Speed measurement accuracy
-10 10 %
Fan speed control range
Linear mode
0 100 %
3