O-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par.O-04 Control Word Timeout Function is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in par.O-04 Control Word Timeout Function and displays a warning, until
par.O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.
[1] *
Resume set-up
Resumes the set-up active prior to the time-out.
O-06 Reset Control Word Timeout
Option:
Function:
This parameter is active only when the choice Hold set-up [0] has been selected in par.O-05 End-of-
Timeout Function .
[0] *
Do not reset
Retains the set-up specified in par.O-04 Control Word Timeout Function, [Select setup 1-4] following a
control time-out.
[1]
Do reset
Returns the drive to the original set-up following a control word time-out. When the value is set to Do
reset [1], the drive performs the reset and then immediately reverts to the Do not reset [0] setting.
O-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for LonWorks.
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
O-10 Control Word Profile
Option:
Function:
Select the interpretation of the control and status words corresponding to the installed network. Only the
selections valid for the network installed in slot A will be visible in the keypad display.
[0] *
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
O-50 Coasting Select
Option:
Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
[0]
Digit Input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or network option module.
[2]
Logic AND
Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] *
Logic OR
Activates Start command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.
AF-600 FP LonWorks
49
8