Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual
Page 26

Alarm Flag
Variable
name:
SNVT
type:
State:
Value:
Command:
nvoAlarm
SNVT_switch
0 (False)
0
No alarm(s) present
1
(True)
100
Alarm(s)
present
This variable indicates whether any alarm is present.
Warning Flag
Variable
name:
SNVT
type:
State:
Value:
Command:
nvoWarning
SNVT_switch
0 (False)
0
No warning(s) present
1
(True)
100
Warning(s)
present
This variable indicates whether any warning is present.
Alarm Word
Variable
name:
SNVT
type:
State:
nvoAlarmword
SNVT_state_64
Boolean 1 bit x 64
This variable contains the complete alarm word.
For more detailed information on the Alarm Word, please refer to the Troubleshooting section of this manual.
NB!
Please note that in the representation of the Alarm Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
Warning Word
Variable
name:
SNVT
type:
State:
nvoWarningword
SNVT_state_64
Boolean 1 bit x 64
This variable contains the complete warning word.
For more detailed information on the Warning Word, please refer to the Troubleshooting section of this manual.
NB!
Please note that in the representation of the Warning Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
AF-600 FP LonWorks
25
5