Af-600 fp lonworks, 3 drive vsd profile – GE Industrial Solutions AF-600 FP Lonworks User Manual
Page 17
5.1.3 Drive VSD Profile
The drive VSD Profile describes all GE drive specific network variables.
Input variables
Variable Function
Variable Name
SNVT type
Profile
AF-600 FP Par.
Start/Stop
nviStartStop
SNVT_switch
Drive VSD
CTW/reference
Control word
nviControlword
SNVT_state
Drive VSD
CTW
Reset fault
nviResetFaut
SNVT_switch
Drive VSD
CTW
Reference [%]
nviRefPcnt
SNVT_lev_percent
Drive VSD
Reference
Reference [Hz]
nviRefHz
SNVT_freq_hz
Drive VSD
Reference
CL Setpoint 1
nviSetpoint1
SNVT_lev_percent
Drive VSD
CL-21
CL Setpoint 2
nviSetpoint2
SNVT_lev_percent
Drive VSD
CL-22
CL Setpoint 3
nviSetpoint3
SNVT_lev_percent
Drive VSD
CL-23
Bus feedback 1
nviFeedback1
SNVT_lev_percent
Drive VSD
O-94
Bus feedback 2
nviFeedback2
SNVT_lev_percent
Drive VSD
O-95
Bus feedback 3
nviFeedback3
SNVT_lev_percent
Drive VSD
O-96
Digital/relay outputs
nviDigiOutput
SNVT_state_64
Drive VSD
E-90
Analog output (42)
nviAnOut1
SNVT_lev_percent
Drive VSD
AN-53
Analog output (X30/8)
nvi101AnOut1
SNVT_lev_percent
Drive VSD
AN-63
Analog output (X42/7)
nvi109AnOut1
SNVT_lev_percent
Drive VSD
AO-43
Analog output (X42/9)
nvi109AnOut2
SNVT_lev_percent
Drive VSD
AO-53
Analog output (X42/11)
nvi109AnOut3
SNVT_lev_percent
Drive VSD
AO-63
Setting of RTC
nviTimeStamp
SNVT_time_stamp
Drive VSD
K-70
Parameter access command nviParamRequest
UNVT_param_request
Drive VSD
-
AF-600 FP LonWorks
16
5