5.3.4 Configuration Properties (nci)
Variable function
Variable name
SNVT type
Profile
AF-600 FP pa-
rameter
Max. motor speed [%]
nciMaxSpeed
SNVT_lev_percent
VSD 6010
F-17
Min. motor speed [%]
nciMinSpeed
SNVT_lev_percent
VSD 6010
F-18
Nom. motor speed [RPM]
nciNmlSpeed
SNVT_rpm
VSD 6010
P-06
Nom. motor frequency [Hz]
nciNmlFreq
SNVT_freq_hz
VSD 6010
F-04
Min. ramp-up time [s]
nciRampUpTime
SNVT_time_sec
VSD 6010
F-07
Min. ramp-down time [s]
nciRampDownTime
SNVT_time_sec
VSD 6010
F-08
Heartbeat time [s]
nciSndHrtBt
SNVT_time_sec
VSD 6010
-
A range of network configuration variables (SCPT's) is available for configuration of the frequency converter parameters. These parameters require setting only
once, usually following installation.
NB!
Please note that the settings written to configuration properties (nci's) will be stored in the non-volatile memory. Continuous writing to configuration properties
may damage the non-volatile memory.
5.4 Network Variable Description - VSD Profile - input
5.4.1 Frequency Converter Speed Setpoint
Variable name:
SNVT type:
State:
Value:
Command:
nviDrvSpeedStpt
SNVT_switch
0 (False)
Any
Stop
1 (True)
0
Running 0 %
1 (True)
1-200
Running 0.5 to 100 %
1 (True)
201-255
Running 100 %
0xFF (default)
Any
AUTO (invalid, no action)
This input variable provides start / stop control and a speed reference.
AF-600 FP LonWorks
30
5