5.5 Network Variable Description - VSD Profile - Output
5.5.1 Drive Speed
Variable
name:
SNVT
type:
Value:
nvoDrvSpeed
SNVT_lev_percent
Min:
Max:
Resolution:
-163.840 %
+163.830 %
0.005 %
This variable contains the frequency converter speed as a percentage of the nominal speed.
5.5.2 Output Current
Variable
name:
SNVT
type:
Value:
nvoDrvCurnt
SNVT_amp
Min:
Max:
Resolution:
0 A
3,276.6 A
0.1 A
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.
5.5.3 Output Voltage
Variable
name:
SNVT
type:
Value:
nvoDrvVolt
SNVT_volt
Min:
Max:
Resolution:
0 V
3,276.6 V
0.1 V
This variable contains the frequency converter output voltage.
5.5.4 Output Power
Variable
name:
SNVT
type:
Value:
nvoDrvPwr
SNVT_power_kilo
Min:
Max:
Resolution:
0 kW
6,554.4 kW
0.1 kW
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
5.5.5 Running Hours
Variable
name:
SNVT
type:
Value:
nvoDrvRunHours
SNVT_time_hour
Min:
Max:
Resolution:
0
hr
65,534
hr
1
hr
This variable contains the total running hours of the motor.