8 parameters, 1 parameter list, 2 parameter group o – GE Industrial Solutions AF-600 FP Lonworks User Manual
Page 48: Af-600 fp lonworks
8 Parameters
8.1 Parameter List
8.1.1 Parameter List
Par. No.
Parameter name:
Default value:
Range:
Conversion
type:
Data type:
O-01
Control Site
Dig. and control word [0]
[0 - 2]
-
5
O-02
Control Word Source
Drive Port [1]
[0 - 4]
-
5
O-03
Control Word Timeout Time
600 s
0.1 - 18000
1
7
O-04
Control Word Timeout Function
Off [0]
[0 - 10]
-
5
O-05
End-of-timeout Function
Hold set-up [0]
[0 - 1]
-
5
O-06
Reset Control Word Timeout
Do not reset [0]
[0 - 1]
-
5
O-07
Diagnosis Trigger
Disable [0]
[0 - 3]
-
5
O-10
Control Word Profile
Drive profile [0]
[0 - x]
-
5
O-50
Coasting Select
Logic OR [3]
[0 - 3]
-
5
O-52
DC Brake Select
Logic OR [3]
[0 - 3]
-
5
O-53
Start Select
Logic OR [3]
[0 - 3]
-
5
O-54
Reversing Select
Logic OR [3]
[0 - 3]
-
5
O-55
Set-up Select
Logic OR [3]
[0 - 3]
-
5
O-56
Preset Reference Select
Logic OR [3]
[0 - 3]
-
5
LN-00
Neuron ID
00 00 00 00 00 00
-
-
10
LN-10
Drive Profile
VSD 6010 [0]
-
-
5
LN-15
Lon Warning Word
0
-
-
6
LN-18
LonWorks Revision
[0, 10]
-
-
9
LN-21
Store Data Values
Off [0]
[0 - 1]
-
5
8.2 Parameter Group O-##
O-01 Control Site
Option:
Function:
The setting in this parameter overrides the settings in par.O-50 Coasting Select to par.O-56 Preset Refer-
ence Select.
[0] *
Digital and ctrl.word
Control by using both digital input and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword only
Control by using control word only.
O-02 Control Word Source
Option:
Function:
Select the source of the control word: one of two serial interfaces or four installed options. During initial
power-up, the drive automatically sets this parameter to Option A [3] if it detects a valid network option
installed in slot A. If the option is removed, the drive detects a change in the configuration, sets
par.O-02 Control Word Source back to default setting Drive Port, and the drive then trips. If an option is
installed after initial power-up, the setting of par.O-02 Control Word Source will not change but the drive
will trip and display: Alarm 67 Option Changed.
[0]
None
[1]
Drive Port
[2]
USB Port
[3] *
Option A
AF-600 FP LonWorks
47