GW-7553 PROFIBUS/Modbus TCP Gateway User Manual (Version 1.00, Dec/2008) PAGE: 53
Step 7: Set the network settings of the GW-7553 by PROFIBUS/Modbus
gateway utility (please refer section 5.5 & 5.6). The settings of the GW-
7553 must have the same domain and different IP with the PC (ex: PC’s
IP=192.168.0.106, MASK=255.255.0.0; GW-7553’s IP=192.168.0.107,
MASK=255.255.0.0).
Step 8: Reset the power of the GW-7553 for an active setting.
4.9.1 Receiving data from a Modbus Master device
-- Start the test utility “MBTCP” (figure 53) on the PC.
This utility simulates a Modbus Master device and is on the web site in the
following directory:
(1) Set the IP address of the GW-7553
(2) Click the connect button
Figure53 MBTCP Utility
--Send Command to write DO of the GW-7553
The user needs to input command (” 01 0F 00 00 00 10 02 FF FF”) here and
click
10 02 FF FF” and then MBTCP can receive response message (” 01 0F 00 00
00 10”). The user can find byte 0, 1 of the input data area in the configuration