GW-7553 PROFIBUS/Modbus TCP Gateway User Manual (Version 1.00, Dec/2008) PAGE: 33


Input Relay/Coil module parameters:

Modbus Slave Device ID(M):1

Start Address(M):9

NO. Of Relay/Coil(M):10

Module Type(M):Read DI

TCP_Connect_Index(T)(M):1

Example 2:
If the user wants to write a Modbus analog output module (AO module), Device
ID is 2, data address is 40001~ 40004 and data count is 4 via the second TCP
connection.

In this case, the user can select an “Output Register => 4 Words module”, module
parameters are shown in the below:

Output Register module parameters:

Modbus Slave Device ID(M):2

Start Address(M):0

TCP_Connect_Index(T)(M):2

PS:

a. Relay/Coil module is digital module (DI/DO module), the unit is Byte;

Register module is analog module (AI/AO module), the unit is Word.

b. Modbus Slave Device ID:It is a Modbus Slave device address.
c. Start Address:The GW-7553 and Modbus Slave device exchange data

from this starting address.

d. NO. of Relay/Coil:It is data size that the GW-7553 and Modbus Slave

device exchange.

e. Module type:The user can select data type for data exchange by this

setting.

„ Write DO(WDO)-- Write Digital Output
„ Write AO(WAO)-- Write Analog Output
„ Read DI(RDI)- Read Digital Input
„ Read DO(RDO)- Read Digital Output
„ Read AI(RAI)-Read Analog Input
„ Read AO(RAO)-Read Analog Output

f. TCP_Connect_Index:The user can select TCP connection of the module.

The module will transmit and receive data from this connection.