GW-7553 PROFIBUS/Modbus TCP Gateway User Manual (Version 1.00, Dec/2008) PAGE: 33
Input Relay/Coil module parameters:
●
Modbus Slave Device ID(M):1
●
Start Address(M):9
●
NO. Of Relay/Coil(M):10
●
Module Type(M):Read DI
●
TCP_Connect_Index(T)(M):1
Example 2:
If the user wants to write a Modbus analog output module (AO module), Device
ID is 2, data address is 40001~ 40004 and data count is 4 via the second TCP
connection.
In this case, the user can select an “Output Register => 4 Words module”, module
parameters are shown in the below:
Output Register module parameters:
●
Modbus Slave Device ID(M):2
●
Start Address(M):0
●
TCP_Connect_Index(T)(M):2
PS:
a. Relay/Coil module is digital module (DI/DO module), the unit is Byte;
Register module is analog module (AI/AO module), the unit is Word.
b. Modbus Slave Device ID:It is a Modbus Slave device address.
c. Start Address:The GW-7553 and Modbus Slave device exchange data
from this starting address.
d. NO. of Relay/Coil:It is data size that the GW-7553 and Modbus Slave
device exchange.
e. Module type:The user can select data type for data exchange by this
setting.
Write DO(WDO)-- Write Digital Output
Write AO(WAO)-- Write Analog Output
Read DI(RDI)- Read Digital Input
Read DO(RDO)- Read Digital Output
Read AI(RAI)-Read Analog Input
Read AO(RAO)-Read Analog Output
f. TCP_Connect_Index:The user can select TCP connection of the module.
The module will transmit and receive data from this connection.