GW-7553 PROFIBUS/Modbus TCP Gateway User Manual (Version 1.00, Dec/2008) PAGE: 36

Table 12 Input data area

Module

Byte

Data

Description

Input

module

0~127

Data Receive data


4.6.2 Output data area and communication command

The maximum length of output data is 131 bytes. Before arrange the output
module, the user must arrange and configure the system setting module. The
first three bytes belong to communication commands, as shown in table 13. The
user can change data and I/O state of Modbus Slave device or DI/DO/AI/AO
data of GW-7553 by modify data of output module.

Table 13 Output data area

Bit Position

Module Byte

7

6

5

4

3

2

1

0

Description

0

Data output command

1

- - - -

-

-

SM DC Control bit

System

setting

module

2

Output module select

Output

module

3~130

Output data

Data output command(byte 0)
a. When Modbus type is Master

When this byte is changed, PROFIBUS Master device will send data
of output module to DO/AO data of GW-7553 and then GW-7553
will send query message to Modbus Slave device for change data or
output state of Modbus Slave device.

b. When Modbus type is Slave

When this byte is changed, PROFIBUS Master device will send data
of output module to DO/AO data of GW-7553.


PS: When the user use this byte to trigger “data output command”, the
user must increase this byte in order (ex: 0->1, 1->2,…, 255->0) or else