beautypg.com

Failsafe timer functionality, Overview field descriptions – Perle Systems Perle IOLAN DS1 User Manual

Page 132

background image

Settings

132

IOLAN DS1/TS2 User’s Guide, Version 3.4

Failsafe Timer Functionality

Overview

The

Failsafe Timer

tab configures the I/O failsafe timer. The Failsafe Timer is enabled on a global

basis and provides a trigger mechanism that can be configured for each channel when no I/O
traffic/management has occurred for the specified amount of time. A Failsafe Action can be
configured for each Digital Output channel, each Serial Signal Output channel (DTR and RTS), and
each Relay channel to either Activate or Deactivate the output.

Field Descriptions

Configure the following parameters:

Embedded

When this option is selected, the address of the slave Modbus device is
embedded in the message header.

Default: Enabled

Remapped

Used for single device/port operation. Older Modbus devices may not include a
UID in their transmission header. When this option is selected, you can specify
the UID that will be inserted into the message header for the Modbus slave
device. This feature supersedes the Broadcast feature.

Default: Disabled

Remap UID

Specify the UID that will be inserted into the message header for the Slave
Modbus serial device.

Range: 1-247

Default: 1

Enable I/O Failsafe
Timer

Enables/disables the Failsafe Timer. This is the global setting that must be
enabled to set the Failsafe Action on the channel for digital outputs and relays.
When this timer expires because of no I/O activity within the specified time
interval, the Failsafe Action set for the channel determines the action on the
output.

Default: Disabled

Timeout

The number of seconds that must elapse with no I/O activity before the channel
Failsafe Action is triggered.

Range: 1-9999

Default: 30 seconds