Panasonic WJ-NT204 User Manual
Page 84
![background image](/manuals/169503/84/background.png)
85
o
ALARM TYPE
This setting specifies the sensor (alarm) input reception
whether to accept or ignore depending on the signal
forms, and applies to all 8 inputs on the rear of the
transmitter. The default setting is EDGE (CLOSE).
LEVEL:
The transmitter enters the alarm mode when
the input retains active (when low) for more than 1
second.
EDGE (OPEN):
The transmitter enters the alarm mode
when the input changes from close to open.
EDGE (CLOSE):
The transmitter enters the alarm mode
when the input changes from open to close.
Note:
The alarm log may record redundant event when
this setting is changed from one to another.
!0
ALARM PORT Enable/Disable SETUP page
Clicking this line opens the setup page.
The sensor inputs connected to the rear of the transmit-
ter unit can be enabled or disabled with this setup. EXT
can be set only for the port #8. This setup is applied
only to the transmitter unit. The default setting is
ENABLE for all ports.
ENABLE:
The unit accepts the sensor input.
DISABLE:
The unit ignores the sensor input.
EXT:
The highest priority is given to #8 port that the
unit ignores inputs to other ports when #8 port is
activated.
!1
ALARM LOG CLEAR
Click this button to clear the alarm log.