3-46

Control of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

4. System Controller

How to connect electrical wiring

(1) Connect B1, B2 to indoor PCB T10 connector using
the accessory 6P connector. (with fuse) (*No polarity)
Total wire length is less than 985 ft. and size is
AWG#18.

(2) Connect B5, B6 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#18.

Basic wiring

Terminals for remote monitoring

Basic wiring diagram of control wiring

A max. of 64 indoor units and 30 outdoor units can be
connected in 1 system.

Up to 10 system controllers can be connected in 1
system.

B1

Indoor unit PCB

T10
(YEL)

2P terminal base

Indoor unit

System controller

Accessory connctor

Wire joint connection

B2

B3

B4

B5

B6

U1

U2

A1

A2

A3

A4

A5

A6

B6

B5

B4

B3

B2

B1

Inter-unit
control wiring

System controller

RC1

1-1

RC2

RC3

2-1

3-1

B1:

B2:

B3:

B4:

B5:

B6:

Power supply: DC12V *No polarity
To T10 connector on indoor PCB

Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity

Auxiliary of inter-unit control wiring

Not be used

A1:

A2:

A3:

Common input for turning air conditioners on or off.

A4:

A5:

A6:

ON operation state indicator output.

Alarm indicator output.

Common indicator output.

Input for turning off air conditioners concurrently.

Input for turning on air conditioners concurrently.

Fig. 3-27

Fig. 3-28

Electrical wiring