Wall-mounted type (k type) – Sanyo CHX03652 User Manual
Page 180
4-70
Mini ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
7. Wall-Mounted Type (K Type)
Unit specifications (E)
MODEL No.
Indoor Unit
KHX2452
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
25,000
27,000
kW
7.3
8.0
Air circulation (Hi / Me / Lo)
CFM
565 / 495 / 350
Moisture removal (High)
Pints / h
7.19
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.37
0.39
0.38
0.32
Power input
W
72
83
72
83
Power factor
%
94
93
91
93
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Air filter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
42 / 38 / 35
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
3 / 8 (9.52)
Gas tube
in. (mm)
5 / 8 (15.88)
Drain connection
13 A, OD 45 / 64”
Remote controller
Optional (RCS-TM80BG, RCS-SH1AAB)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 3.0Y 8.6 / 0.8, RAL 9002-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
13 (330)
15-11 / 32 (390)
Width
in. (mm)
44-7 / 8 (1140)
47-27 / 32 (1215)
Depth
in. (mm)
8-31 / 32 (228)
11-17 / 32 (293)
Net weight
lbs. (kg)
46 (21)
Shipping weight
lbs. (kg)
53 (24)
Shipping volume
ft
3
(m
3
)
4.9 (0.139)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
chap_04-07-1.indd 70
2007/07/23 13:37:32