Concealed duct type (u type) – Sanyo CHX03652 User Manual
Page 145
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4-35
Mini ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4. Concealed Duct Type (U Type)
Unit specifications (C)
MODEL No.
Indoor Unit
UHX1852
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
19,000
21,000
kW
5.6
6.3
Air circulation (Hi / Me / Lo)
CFM
420 / 370 / 320
Moisture removal (High)
Pints / h
6.34
–
External static pressure (High)
in. WG
0.16 : At shipment 0.25 : Using the booster cable
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.52
0.55
0.48
0.51
Power input
W
101
118
94
111
Power factor
%
93
93
94
95
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Air filter
Field supply
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
30 / 28 / 25
Using the booster cable (Hi / Me / Lo)
dB-A
33 / 30 / 28
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
25 A, OD 1-1 / 4”
Drain pump
Max. head 1.6 ft. above drain connection
Remote controller
Optional (RCS-TM80BG, RCS-BH80AAB.WL)
Refrigerant tubing kit / Accessories
Optional / Booster cable
Color (Approximate value)
–
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
12-7 / 32 (310)
14-3 / 32 (358)
Width
in. (mm)
27-9 / 16 (700)
35-3 / 32 (891)
Depth
in. (mm)
24-13 / 16 (630)
30-13 / 16 (783)
Net weight
lbs. (kg)
55 (25)
Shipping weight
lbs. (kg)
64 (29)
Shipping volume
ft
3
(m
3
)
8.8 (0.250)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
chap_04-04-1.indd 35
2007/07/23 13:30:40