Model selecting and capacity calculator – Sanyo CHX03652 User Manual
Page 14
2-6
Design of Mini ECO-i SYSTEM
1
2
3
4
5
6
7
8
Refer to the graph below for the correction coefficients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling)
Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Indoor unit capacity correction coef
ficient
Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
Note: When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
5. Graph of capacity correction coefficients
■ Graph of outdoor unit capacity characteristics (1 – (1))
Outdoor unit cooling capacity characteristics
14
120
71˚F WB
66˚F WB
60˚F WB
100
80
95
100
109
80
90
100
104
(1)
(2)
(1)
(2)
(2) CHX06052
(1) CHX03652
Capacity r
atio (%)
Outdoor air intake temp. (˚F DB)
1. Model Selecting and Capacity Calculator