Model selecting and capacity calculator, Design of mini eco-i system – Sanyo CHX03652 User Manual
Page 19
2-11
1
2
3
4
5
6
7
8
Design of Mini ECO-i SYSTEM
1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
92 90
88
86
84
82
80
78
76
0
33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
Ele
vation diff
erence (ft)
Equivalent length (ft)
164
131
98
66
33
0
–33
–66
–98
–131
*1
97
96
95
94
93
92
91
0
33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
164
131
98
66
33
0
–33
–66
–98
–131
Ele
vation diff
erence (ft)
*1
98
99
100
%
Equivalent length (ft)
Base capacity
change rate (%)
Base capacity
change rate (%)
94
100
%
98
96
Inverter model rated performance values
Cooling
Heating
Item
Model
CHX03652
CHX06052
Cooling
capacity
BTU/h(kW)
BTU/h(kW)
BTU/h(kW)
BTU/h(kW)
Power
consumption
Heating
capacity
Power
consumption
38,200 (11.2)
52,900 (15.5)
9,400 (2.76)
15,600 (4.57)
42,700 (12.5)
60,000 (17.6)
9,800 (2.88)
15,600 (4.58)
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3))
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
Outdoor intake air –4
5
14
17
21
23
24
28
30
32
33
35
37
39
41
42
temp.
(°F WB RH 85%)
Correction
0.97
0.97
0.97
0.96 0.94
0.91 0.89
0.87
0.87
0.87
0.88
0.89
0.91
0.92 0.95
1.0
coefficient
1. Model Selecting and Capacity Calculator
05-231 Mini ECO-i T_D 2_0116.ind11 11