Concealed duct type (u type) – Sanyo CHX03652 User Manual
Page 149
4-39
Mini ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
4. Concealed Duct Type (U Type)
Indoor unit (B)
MODEL No.
UHX1252
Power source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-UXRP71B-B (Microprocessor)
Fan...(Number diameter / length in. (mm))
Centrifugal (1 ... ш7-31/64 (ш190))
Fan motor
Model...Nominal output
W
SFG4X-51C6P...50 W
Power source
208 - 230 V / 1ø / 60 Hz
No. of pole...r.p.m. (230V, High)
rpm
4P... 834
Coil resistance
(Ambient temperature 68°F)
Ω
BRN – WHT :
86.0
ORG – YEL :
15.9
WHT – VLT :
13.4
YEL – BLK :
30.1
VLT – ORG :
23.4
BLK – PNK :
27.5
Run capacitor
VAC, µF
450 VAC, 1.5 µF
Safety device
fuse
Operating temperature
Open °F (°C)
266 ± 9 (130 ± 5)
Close °F (°C)
181 ± 27 (83 ± 15)
Electronic expansion valve
Coil
UKV-U031E
Coil resistance (at 68°F)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-18D31
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fin pitch
in. (mm)
2...1 / 16 (1.5)
Face area
ft
2
(m
2
)
1.22 (0.113)
Drain pump
PLD-12230ST
Rated
V, Hz, W
AC230V, 60Hz, 10.8W
Total head & capacity
in. (mm), gal/
min (cc/min)
19-11 / 16 (500), 0.11 (400)