4-way air discharge semi-concealed type (x type) – Sanyo CHX03652 User Manual
Page 129
4-19
Mini ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
2. 4-Way Air Discharge Semi-concealed Type (X Type)
Indoor unit (D)
MODEL No.
XHX3652
Power source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-SXRP56B-B (Microprocessor)
Fan...(Number diameter / length in. (mm))
Turbo (1...ш18-7/64 (ш460))
Fan motor
Model...Nominal output
W
DK8-93C280HB...90 W
Power source
280 VDC
No. of pole...r.p.m. (230V, High)
rpm
8P...540
Coil resistance
(Ambient temperature 68°F)
Ω
RED – WHT : 43.0
WHT – BLU : 43.0
BLU
– RED : 43.0
Run capacitor
VAC, µF
–
Safety device
fuse
Operating temperature
Open °F (°C)
285
+4
–5
(141
+2
–3
)
Electronic expansion valve
Coil
UKV-U030E
Coil resistance (at 68°F)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-30D33
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fi n pitch
in. (mm)
2...3/64 (1.25)
Face area
ft
2
(m
2
)
6.29 (0.584)
Panel
Model No.
PNR-XH3652
Auto louver motor
MP24ZN
Coil resistance (at 77°F)
Ω
380
Ω ± 7% / phase
Drain pump
PLD-12230ST
Rated
V, Hz, W
AC230V, 60Hz, 10.8W
Total head & capacity
in. (mm), gal/
min (cc/min)
25-3/16 (640), 0.11 (400)