4-67
Mini ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
7. Wall-Mounted Type (K Type)
Unit specifications (B)
MODEL No.
Indoor Unit
KHX0952
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
9,600
11,000
kW
2.8
3.2
Air circulation (Hi / Me / Lo)
CFM
350 / 280 / 210
Moisture removal (High)
Pints / h
3.38
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.20
0.21
0.20
0.21
Power input
W
50
56
50
56
Power factor
%
96
94
96
94
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Air filter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
36 / 32 / 28
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
13 A, OD 45 / 64”
Remote controller
Optional (RCS-TM80BG, RCS-SH1AAB)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 3.0Y 8.6 / 0.8, RAL 9002-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
11-7 / 32 (285)
13-21 / 32 (347)
Width
in. (mm)
39-3 / 16 (995)
41-15 / 16 (1065)
Depth
in. (mm)
8 (203)
10-1 / 4 (260)
Net weight
lbs. (kg)
31 (14)
Shipping weight
lbs. (kg)
35 (16)
Shipping volume
ft
3
(m
3
)
3.4 (0.096)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
chap_04-07-1.indd 67
2007/07/23 13:37:32