6. Ceiling-Mounted Type (T Type)
Unit specifications (C)
MODEL No.
Indoor Unit
THX2452
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
25,000
27,000
kW
7.3
8.0
Air circulation (Hi / Me / Lo)
CFM
650 / 530 / 495
Moisture removal (High)
Pints / h
6.34
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.34
0.31
0.34
0.36
Power input
W
38
37
40
40
Power factor
%
54
52
57
48
Max. starting amperes
A
2
2
2
2
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Air filter
Washable, easy access, long life (2,500hr)
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
38 / 36 / 33
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
3 / 8 (9.52)
Gas tube
in. (mm)
5 / 8 (15.88)
Drain connection
25 A, OD 1-1 / 32”
Remote controller
Optional (RCS-TM80BG, RCS-TRP80AAB.WL)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 10Y9.0 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
8-9 / 32 (210)
11-1 / 32 (280)
Width
in. (mm)
46-15 / 32 (1180)
49-13 / 32 (1255)
Depth
in. (mm)
26-25 / 32 (680)
30-23 / 32 (780)
Net weight
lbs. (kg)
55 (25)
Shipping weight
lbs. (kg)
62 (28)
Shipping volume
ft
3
(m
3
)
9.7 (0.274)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
chap_04-06-1.indd 59
2007/07/23 13:35:34