Electrical wiring – Sanyo CHX03652 User Manual
Page 208
5-20
Test Run and Others
1
2
3
4
5
6
7
8
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
more than 3.3 ft.
more than 3.3 ft.
Branch
point
16 or fewer
Indoor unit
Indoor unit
Indoor unit
Indoor unit
less than 3.3 ft.
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
NO
NO
Branch point
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no
connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-13)
Outdoor unit
Outdoor unit
Outdoor unit
Prohibited
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 5-13
Fig. 5-14
Fig. 5-15
CAUTION
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address
setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 5-15)
3. Electrical Wiring