4-53
Mini ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
5. Concealed Duct High-Static Pressure Type (D Type)
Indoor unit (B)
MODEL No.
DHX4852
Power source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-UXRP71B-B (Microprocessor)
Fan...(Number diameter / length in. (mm))
Centrifugal (1 ... ш7-31/64 (ш220))
Fan motor
Model...Nominal output
W
KFC4Q-401A6P...400 W
Power source
208 - 230 V / 1ø / 60 Hz
No. of pole...r.p.m. (230V, High)
rpm
4P... 1,077
Coil resistance
(Ambient temperature 68°F)
Ω
WHT – BRN : 11.05
WHT – VLT : 1.796
VLT – ORG : 1.002
ORG – YEL : 4.574
YEL – PNK : 7.699
Run capacitor
VAC, µF
440 VAC, 7.0 µF
Safety device
fuse
Operating temperature
Open °F (°C)
266 ± 9 (130 ± 5)
Close °F (°C)
181 ± 27 (83 ± 15)
Electronic expansion valve
Coil
UKV-U030E
Coil resistance (at 68°F)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-30D33
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fin pitch
in. (mm)
4...5 / 64 (2.0)
Face area
ft
2
(m
2
)
3.02 (0.281)
chap_04-05-2.indd 53