beautypg.com

Fan and deflector requirements – Motorola 3460 User Manual

Page 26

background image

3460 Fast’R

1-12

Fan and Deflector Requirements

Forced-air cooling for up to four rack-mounted enclosures can be
provided by fans and a deflector, mounted below the enclosures, to
provide passive, bottom-entry rear exhaust and upward-forced, front-
entry cooling air. Refer to Figure 1-6. The airflow requirement is 80
CFM (2266230 CCM).

For example, three fans rated 117 CFM (202176 CCM) at a static
pressure of 0 inches of water provide enough airflow, when cooling four
enclosures. The deflector ensures that hot air from equipment below the
enclosures does not mix with enclosure-cooling air. The cabinet must
have venting at the top or rear to let exhaust air escape.

Figure 1-6. Cabinet Arrangement

Three or More Enclosures

Unit 2

Fan Chassis 2

Unit 1

Fan Chassis 1

AccessWay

AccessWay

AccessWay

AccessWay