68bprint alarm list, Create trigger – Honeywell EN2Z-0906GE51 R0708 User Manual
Page 89

USER GUIDE
ARENA/ RANGER
89
EN2Z-0906GE51
R0708
a. In Arena, select the remote ARENA you want to forward the alarms.
b. In Destination name, enter a descriptive text for the ARENA.
16. Click Advanced tab.
Advanced
Tab
Behavior on Connection Failure
a. In Retry count, enter the number of attempts ARENA should make to reach
the remote ARENA. When ARENA still cannot reach the remote ARENA after
retrying, it stops any further attempt until a new alarm comes in.
b. In Retry interval (minutes), enter interval in minutes the ARENA waits
between the retry attempts.
17. Click the OK button.
18. Continue with creating the trigger conditions as described in the “Create Trigger”
section.
Create Trigger
A trigger is the condition (event) that causes ARENA to forward an alarm if the
condition becomes true.
Example:
If the alarm severity (property) is critical (condition), any critical alarms will be
forwarded.
1. Hover the cursor over the Configuration menu icon
and click Alarming
in the configuration menu.
2. Select
the
Forwarding
tab and click Create new Trigger button, or select the
Trigger
tab and click Create Trigger button. The Trigger tab displays. Here you
create the conditions for triggering the alarm forwarding by doing the following: