ProSoft Technology 5201-DFNT-104C User Manual
Page 87
![background image](https://www.manualsdir.com/files/866222/content/doc087.png)
104C Version 3 ♦ ProLinx Gateway
Mailbox Feature (x201-DFNT-104C)
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 87 of 139
August 4, 2011
4.9
Reset Status Data Mailbox (9997)
This mailbox requests the module to reset all status counters
Mailbox Request
Word Offset in
Block
Data Field(s)
Description
0
Mailbox ID
This field contains the value of -9997 or
9997 identifying the block type to the
module.
1
Reset Module
Status
Set a value of 1 to reset the module
status
2
Reset Client 1
Status
Set a value of 1 to reset client 1 status
3
Reset Client 2
Status
Set a value of 1 to reset client 2 status
4
Reset Client 3
Status
Set a value of 1 to reset client 3 status
5
Reset Client 4
Status
Set a value of 1 to reset client 4 status
1 to 62
Not Used
Not Used
63
Mailbox ID
This field contains the value of -9997 or
9997 identifying the block type to the
module.
Mailbox Response
Word Offset in
Block
Data Field(s)
Description
0
Mailbox ID
This field contains the value of -9997 or
9997 identifying the block type to the
module.
1 to 62
Reserved
Reserved
63
Mailbox ID
This field contains the value of -9997 or
9997 identifying the block type to the
module.