ProSoft Technology 5201-DFNT-104C User Manual
Page 19
104C Version 3 ♦ ProLinx Gateway
Configuring the Gateway
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 19 of 139
August 4, 2011
Time Zone
-11 to 11
This parameter specifies the time zone offset to be used from the UTC time
zone. A value of zero uses UTC time. If the value entered is positive, the time
zone is west of the UTC time zone (for example, Eastern Standard Time is 5). If
the value entered is negative, the time zone is east of the UTC time zone (for
example, Continental Europe is -1).
Use Daylight Savings Time
Y
ES
or N
O
This parameter specifies if daylight savings time will be used in the time
computation.
Database Register
-1 or 0 to 3996 as an even value
This parameter specifies if the NTP time computed by the driver is to be placed
into the module’s database. If a value of -1 is specified, the time will not be
placed into the database. If the value is between 0 and 3992, the time will be
placed in the database. The first 4 bytes will represent the seconds since
1/1/1970, and the second 4 bytes will represent the number of microseconds. An
even value should be used for the register value in order for the data to be stored
correctly.
2.1.2 [IEC-870-5-104]
This section provides the parameters required for general driver configuration.
Most entries contained within this section are self-explanatory.