ProSoft Technology 5201-DFNT-104C User Manual
Page 84
Mailbox Feature (x201-DFNT-104C)
104C Version 3 ♦ ProLinx Gateway
Protocol Manual
IEC 60870-5-104 Client (Firmware v3.xx)
Page 84 of 139
ProSoft Technology, Inc.
August 4, 2011
Mailbox Response
Word Offset in
Block
Data Field(s)
Description
0
Mailbox ID
This field contains the value of -9970 or 9970
identifying the block type to the module.
1
Year
This field contains the four-digit year to be used
with the new time value.
2
Month
This field contains the month value for the new
time. Valid entry for this field is in the range of 1 to
12.
3
Day
This field contains the day value for the new time.
Valid entry for this field is in the range of 1 to 31.
4
Hour
This field contains the hour value for the new time.
Valid entry for this field is in the range of 0 to 23.
5
Minute
This field contains the minute value for the new
time. Valid entry for this field is in the range of 0 to
59.
6
Seconds
This field contains the second value for the new
time. Valid entry for this field is in the range of 0 to
59.
7
Milliseconds
This field contains the millisecond value for the new
time. Valid entry for this field is in the range of 0 to
999.
8 to 62
Not Used
Not Used
63
Mailbox ID
This field contains the value of -9970 or 9970
identifying the block type to the module.