Mailbox Feature (x201-DFNT-104C)

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 82 of 139

ProSoft Technology, Inc.

August 4, 2011

Mailbox Response

Word
Offset in
Block

Data Field(s)

Description

0

Mailbox ID

This field contains the value of -9950 or 9950
identifying the block type to the module.

1

Number of
Commands
reported

This field contains the number of commands
contained in the block that need to be
processed by the PLC. This field will have a
value of 1 to 60.

2

Start Index of First
Command

This field contains the index in the command list
for the first value in the file. This field will have a
value of 0 to MaxCommands-1.

3 to 62

Command List
Errors

Each word of this area contains the last error
value recorded for the command. The
command index of the first value (offset 4) is
specified in word 3 of the block. The number of
valid command errors in the block is set in word
2 of the block. Refer to the command error list
to interpret the error codes reported.

63

Mailbox ID

This field contains the value of -9950 or 9950
identifying the block type to the module.