Time DB Offset
-1 or 0 to 3994
This parameter sets the location in the database where the gateway’s
104C
Client date and time will be copied to.
Note: The following table lists the 12-byte data area placed in the database if the Time DB Offset
parameter is set to a value other than -1:
Byte
Length
Range
Description
0 to 1
2
0 to 59,999
Seconds and milliseconds
2
1
0 to 59
Minutes
3
1
0 to 23
Hour
4
1
Reserved
5
1
1 to 31
Day of the month
6
1
1 to 12
Month
7 to 8
2
0 to 65,535
Year (four-digit format, for example 2005)
9
1
Reserved
10
1
0 or 1
Invalid flag (0 = Valid, 1 = Invalid)
11
1
Reserved
Driver Status Offset
0-3982
Database location of general client driver status data
Disable = -1
Refer to section 6.3 (Server Error and Status Data) for the detailed contents of
the status block.
NOTE: requires 18 registers
Mailbox Offset
0 - 3872
Database offset to the mailbox interface area. This feature is applicable to the
5201-DFNT-104C module. The mailbox allows the DFNT driver to request
specific tasks from the 104 driver such as time update and dynamically sending
commands
Disable = -1
Refer to section 4 (Mailbox feature) for further information about the mailbox
functionality.