104C Version 3 ♦ ProLinx Gateway
Mailbox Feature (x201-DFNT-104C)
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 69 of 139
August 4, 2011
The same applies for the mailbox response. The module builds the mailbox
response and updates the mailbox ID according to the originating request:
Offset
Description
0
Mailbox ID
1
Start of mailbox response
…
…
62
End of mailbox response
63
Mailbox ID
The following mailboxes are supported by the module:
Block Range
Descriptions
±9901
User Constructed Command to add to command queue
±9902
Command Control Block (Add command to Command Queue)
±9903
Event Messages from Outstations
±9250
General Module Status
±9251
Client X Status Data
±9950
Command List Error data
±9970
Get 104 client driver's time
±9971
Set 104 client driver's time
±9997
Reset status data
9998
Cold boot Confirmation
9999
Cold Boot Request
The purpose for the mailbox supporting a positive and negative value is so the
remote device can trigger consecutive requests for the same mailbox by
switching the value between positive and negative. For example, to request 3
consecutive Get Module time the block ID could be switched as +9970, -9970,
+9970.