104C Version 3 ♦ ProLinx Gateway

Configuring the Gateway

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 23 of 139

August 4, 2011

Response Timeout
0 to 5000 milliseconds DEFAULT VALUE = 5000
This parameter sets the maximum number of milliseconds to wait for a
confirmation from the controlled station to a request from this module to
application level messages.

ACTTERM with Set Point
Y - Y

ES

or N - N

O

This parameter determines if an ACTTERM (Activation Termination) will be sent.
If the parameter is set to Y

ES

, then Set point commands will issue an ACTTERM

when the command is complete. If the parameter is set to N

O

, ACTCON

(Activation Confirmation) is the last response to a Set point command.

Status Offset
Range -1 to 3956
Database location of client status data
Range = 0 - 3956
Disable = -1
(Refer to the status section for further information about the content of this
section).

NOTE: requires 44 registers