Mailbox Feature (x201-DFNT-104C)

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 74 of 139

ProSoft Technology, Inc.

August 4, 2011

Mailbox Response

Word Offset in
Block

Data Field(s)

Description

0

Mailbox ID

This field contains the value of -9903
or 9903 identifying the block type to
the module.

1

Event Count

This field contains the number of
events present in the block. Values
of 0 to 4 are valid.

2 to 15

Event 1

Event message

16 to 29

Event 2

Event message

30 to 43

Event 3

Event message

44 to 57

Event 4

Event message

58 to 60

Spare

Not Used

61

Event Count
Remaining

Number of events still present in the
event queue after removing these
events.

62

Event Overflow

This flag will be set if the event buffer
overflowed since last reported.

63

Mailbox ID

This field contains the value of -9903
or 9903 identifying the block type to
the module.

The format of each 14 word data region in the block is as
follows:

Word Offset

Definitions

Description

0

Session Index

This field contains the session index
used to define the controlled unit in
the module from which the event was
generated.

1

Sector Index

This field contains the sector index
used to define the database within the
controlled unit from which the event
was generated.

2

COT

This field contains the COT for the
event message received from the
IED. If the size of the COT is a single
byte, the originator address will
always be zero. The COT is in the
LSB and the originator address is in
the MSB.