ProSoft Technology 5201-DFNT-104C User Manual
Page 30
Configuring the Gateway
104C Version 3 ♦ ProLinx Gateway
Protocol Manual
IEC 60870-5-104 Client (Firmware v3.xx)
Page 30 of 139
ProSoft Technology, Inc.
August 4, 2011
Poll Interval
This parameter is used if the Enable Code field is set as Enabled With Poll
Interval. It sets the minimum number of seconds to delay between successive
execution of the command.
Session
This parameter is utilized to associate the command with one of the
sessions/clients defined for the module.
Sector
This parameter is used to associate the command with the proper sector of the
selected session.
Data Type
This parameter is used to set the ASDU data type to be used with the message.
The codes specified are those defined for the IEC-870-5-101 protocol. The
following is a listing of command control data types supported in this module:
Type Description
---- -------------------------------------------------
45 Single point command
46 Double point command
47 Regulating step point command
48 Setpoint, normalized point command
49 Setpoint, scaled point command
50 Setpoint, short float point command
51 Bitstring (32-bits) point command
100 General or group interrogation command
101 Counter interrogation command
102 Read command
103 Clock synchronization command
105 Reset process command
107 Test command (IEC-870-5-104 type)
110 Parameter setting for normalized measured value
111 Parameter setting for scaled measured value
112 Parameter setting for short float value
113 Parameter activation command